Effect of variable air flow on the energy efficiency of a centralized combustion air system

 

Na minha lista:
Detalhes bibliográficos
Autores: Marrero-Ramírez, Secundino, Vega-Areas, Orlando, González-Palau, Iliana Antonia
Formato: artículo original
Estado:Versión publicada
Fecha de Publicación:2023
Descrição:The research analyzes how manual control in the combustion air system in furnaces of a metallurgical plant can generate energy overconsumption, by using the throttling of a damper with the use of manipulated valves to manually regulate the air flow. Where the system’s centrifugal fans work all the time at full capacity and this produces electrical energy losses, due to the system’s operating dynamics. The demand of the system is variable and its programming is difficult, for this reason an alternative was evaluated that consists of controlling the activation of the fans through variable speed drives with an integral proportional control loop that allows establishing the air flow through non-direct measurement of airflow, using variable pressure to achieve a 30% reduction in power demand with the control system.
País:Portal de Revistas TEC
Recursos:Instituto Tecnológico de Costa Rica
Repositorio:Portal de Revistas TEC
Idioma:Español
OAI Identifier:oai:ojs.pkp.sfu.ca:article/6295
Acesso em linha:https://revistas.tec.ac.cr/index.php/tec_marcha/article/view/6295
Palavra-chave:Flow
fans
control
energy efficiency
motors
Flujo
ventiladores
eficiencia energética
motores